ASSESSMENT OF THE PHYSICOCHEMICAL WATER QUALITY COMPLIANCE OF WUPA WASTEWATER TREATMENT PLANT, FOR DOMESTIC USE IN FEDERAL CAPITAL TERRITORY, ABUJA NIGERIA
Loading...
Date
Authors
Journal Title
Journal ISSN
Volume Title
Publisher
DEPARTMENT OF GEOGRAPHY FACULTY OF ENVIRONMENTAL SCIENCE NASARAWA STATE UNIVERSITY, KEFFI
DOI
Abstract
This study assessed the Physicochemical Water Quality Compliance of Wupa Waste
Water treatment Plant for Domestic use in Federal Capital Territory Abuja, Nigeria.
The aim was achieved through the following objectives: Determine the
physicochemical properties of the water in WUPA waste water treatment. To
determine the suitability of water discharged from Wupa treatment plant for domestic
water use. Methodology, the study was anchored on qualitative research design.
Analysis was carried out in the laboratory and the result obtained from the test were
qualitatively compared with the recommended water quality standard. Parameters
analyzed include: pH, Temperature, Total Dissolved Solid (TDS), Total Suspended
Solid (TSS), Biochemical Oxygen Demand (BOD), Dissolved Oxygen (DO),
Chemical Oxygen Demand (COD), Chloride, Sulphate, Oil and Grease. The study
revealed that the result of the selected physicochemical parameters when further
compared to world Health Organization \TOO (2007) and NESREA (2011) Standard
limit for drinking water showed that all parameters for treated waste water (effluent)
are within the permissible limits for drinking water, except for DO (6.81 mg/I) BOD
(37.3mg/l) and Oil/Grease (13.2mg/l) compared to WHO limits of DO (2mg/l), BOD
(34mg/l) oil/grease (10mg/l) indicate a slight differences in the BOD and Oil/Grease
from the standard limits set by WHO. The result of physicochemical parameters for
each sample were analyzed using simple descriptive statistics of mean, standard
Deviation, and standard error of the mean. The mean score of each analyzed
parameter from each sampling point was compared with the various permissible limits
set by Federal Environmental Protection Agency FEPA (1991) and national
environmental Standard and Regulation Enforcement Agency (NESREA) 2011 in
order to determine the rate of environmental degradation and compounded health
hazards associated to the discharge of Wupa treatment Plant. Thus more effort should
be put in the treatment of influent waste water generated in the F.C.T before discharge
into receiving streams, people using the water downstream of the river Wupa must
treat it or boil it thoroughly and filter before drinking and putting to other domestic
usage.
Description
Keywords
Citation
A DISSERTATION SUBMITTED TO THE SCHOOL OF POSTGRADUATE STUDIES, NASARAWA STATE UNIVERSITY, KEFFI IN PARTIAL FULFILMENT OF THE REQUIREMENTS FOR THE AWARD OF MASTER OF SCIENCE DEGREE IN ENVIRONMENTAL RESOURCE MANAGEMENT DEPARTMENT OF GEOGRAPHY FACULTY OF ENVIRONMENTAL SCIENCES NASARAWA STATE UNIVERSITY, KEFFI